G9802 Duct Air Leakage Tester with Touchscreen Control

Features

  • Air Flow Large Nozzle Range41 ~ 483 CFM
  • Air Flow Small Nozzle Range2.4 ~ 41 CFM
  • Air Flow Accuracy± (2.5% of reading +0.06 CFM)
  • Air Flow Resolution0.01 CFM
  • Static Pressure Range± 10 in. wg

 

Scope of Delivery

  • Duct Air Leakage Tester
  • Low flow nozzle
  • ⌀6 Silicone tube (Blue) 4m
  • Duct connection hose
  • Storage box
  • Power cord
  • Calibration Certification
  • Operation manual

Description

Features

  • Airflow & Pressure Accuracy: High-precision measurement for HVAC duct systems
  • Real-Time Display: Instant graphical and numerical data visualization
  • Portable Design: Wheel-mounted unit for convenient on-site mobility
  • Standards Compliance: SMACNA, BS EN 12237:2003 (EU), BS EN 1507:2006 (EU), DW/143 (EU), Eurovent 2/2 (EU), and GB50243
  • Data Logging: Integrated storage for up to 1000 test records
  • Touchscreen Interface: User-friendly control for simplified operation
  • 1 Year manufacturer’s warranty

TECHNICAL SPECIFICATIONS

Air Flow Large Nozzle Range 41 ~ 483 CFM
Air Flow Small Nozzle Range 2.4 ~ 41 CFM
Air Flow Accuracy ± (2.5% of reading +0.06 CFM)
Air Flow Resolution 0.01 CFM
Static Pressure Range ± 10 in. wg
Static Pressure Accuracy ± (1% of reading +0.004 in. wg.)
Static Pressure Resolution 0.001 in. wg
Temperature Range 32ºF ~ 140ºF
Temperature Accuracy ±1ºF
Temperature Resolution 0.1ºF
Atmospheric Pressure Range 20.6 ~ 38.3 in. Hg
Atmospheric Pressure Accuracy ± 2% of reading
Atmospheric Pressure Resolution 0.1 in. Hg
Power Supply (100-120V, 1 Phase) 50 / 60 Hz, 16A
Power Supply (200-240V, 1 Phase) 50 / 60 Hz, 16A
Weight Net weight approximately 60kg
Dimensions (WxDxH) 18.9 x 24.7 x 44.3 inches
Data Logging Up to 1000 measurements

SERVICES

PERFORMANCE YOU TRUST

DATASHEET

PACKAGING INFO

Width 63 cm
Length 48 cm
Height 113 cm
Weight 60 Kg